Maddalena MICROCLIMA S3C

Maddalena MICROCLIMA S3C

MicroClima S3C is the separate electronic unit for the heat meter.
In addition to its great adaptability, it offers excellent performance in the measurement of both heating and cooling units. The calculation unit must be connected to a pair of temperature probes and a MI-004 certified flow meter.

MICROCLIMA S3C

SEPARATE CALCULATOR FOR COMBINED THERMAL ENERGY METERS

• Compact design
• Replaceable battery, may be connected to a 3 V power pack
• Point of installation (inlet/outlet) may be set on site
• LCD display
• Selectable installation point (flow/return)
• Battery life 10 years
• Can also use an external power supply
• Heating/cooling versions also available
• Retrofit communication interfaces:
– wireless M-Bus*
– wireless M-Bus + 3 pulse inputs*
– M-Bus*
– M-Bus + 3 pulse inputs*
– 2 pulse outputs*
– LoRaWAN + 3 pulse inputs
– Modbus*
* can also be installed later

 

Parameter Specification
Temperature range of medium – heating 0 °C to +150 °C
Temperature range of medium – cooling 0 °C to +50 °C
Operating ambient temperature +5 °C to +55 °C at 95% relative humidity
Transport temperature -25 °C to +70 °C (max. 168 hours)
Storage temperature -25 °C to +55 °C
Temperature difference range ΔΘ (heating) 3 K to 100 K
Temperature difference range ΔΘ (cooling) -3 K to -50 K
Minimum temperature difference ΔΘ (heating) > 0.05 K
Minimum temperature difference ΔΘ (cooling) < -0.05 K
Minimum temperature difference ΔΘ HC (heating/cooling) > 0.5 K / < -0.5 K
Temperature resolution 0.01 °C
Energy measuring cycle Standard operation: 60 s (10-year battery life)
Optional: 30 s (6 + 1-year battery life)
With power pack: 2 s
Pulse options (optional) 1 / 2.5 / 10 / 25 / 100 / 250 / 1000 / 2500 litres per pulse
Display LCD – 8 digits + special characters
Decimals Up to 3 decimal places
Units of measurement MWh, kW, m³, m³/h (kWh, GJ, l, MMBTU, Gcal). The energy unit can be changed while the energy value is ≤ 10 kWh.
Interfaces Standard: Optical interface (M-Bus protocol)

Optional: Wireless M-Bus; Wireless M-Bus + 3 pulse inputs; M-Bus; M-Bus + 3 pulse inputs; 2 pulse outputs; LoRaWAN + 3 pulse inputs; Modbus.

Power supply Replaceable 3 V lithium battery; all models are prepared for a 3 V power pack (input voltage 230 V / 24 V)
Estimated lifetime 10 years (standard); 6 + 1 years (optional). See “Factors Influencing Battery Lifetime” in Maddalena technical documentation.
Data storage Nonvolatile memory
Reading dates Selectable yearly reading date;
15 monthly and semi-monthly values via display or Wireless M-Bus (compact mode);
24 monthly and semi-monthly values via optical interface or M-Bus.
Tariff registers 2 individually configurable registers for energy or time accumulation
Storage of maximum values Power, temperatures (inlet, outlet, ΔΘ), and related maximum values for the last 15 months
Protection class IP54
CE marking Yes
Mechanical class M2
Electromagnetic class E2
Pulse input interface CMOS microcontroller, Class IB, compliant with EN 1434-2:2015 (D)
Medium Standard: Water
Optional (not certified*): Water with 20%, 30%, 40%, or 50% propylene glycol or ethylene glycol. Glycol type and concentration can be configured while the energy value is ≤ 10 kWh.
Weight 0.350 kg
Dimensions (H × L × D) 150 × 130 × 35 mm
Water Meter
Parameter Specification
Pulse output device class EN 1434-2:2015 compliant: OA (reed switch contact); OC (open collector)
Maximum input frequency 10 Hz
Pulse length Minimum 25 ms
Pulse pause Minimum 50 ms

 

Temperature Sensors
Parameter Specification
Sensor type Platinum precision resistor Pt 500
Cable length (unshielded) Up to 10 m for two-wire cables (standard: 3 m; 10 m on request)
Mounting Direct or in pocket